TRIPHASE
AUTO-TRANSFORMERS
ATT
SERIES
SPECIFICATIONS
-
conform to
standard CEI 14/8 EN IEC 989-76 CE
-
sheet with low
loss
-
electrolytic
conductor in thermal class H 200°
- the
thermal insulation class is
E
-
level of insulation is 2 Kv
-
maximum current at full load 3,6 A/mm²
-
standard and bolted clamps
VOLTAGE
TO THE PRIMARY: 230-400 Vca + N
VOLTAGE
TO THE SECONDARY:
on request
POWER KVA |
CODE |
Dimensions AxBxC DI in
mm |
Total losses W |
Weight Kg |
EURO PRICE |
1 KVA |
ATT 1 KVA |
180X90X170 |
20 |
5,1 |
--- |
2 KVA |
ATT 2 KVA |
180X110X170 |
60 |
9,1 |
--- |
3 KVA |
ATT 3 KVA |
180X120X170 |
69 |
11 |
--- |
4 KVA |
ATT 4 KVA |
240X130X200 |
83 |
15 |
--- |
5 KVA |
ATT 5 KVA |
340X130X200 |
92 |
17 |
--- |
6 KVA |
ATT 6 KVA |
240X140X200 |
97 |
23 |
--- |
8 KVA |
ATT 8 KVA |
300X120X270 |
113 |
27 |
--- |
10 KVA |
ATT 10 KVA |
300X130X270 |
120 |
36 |
--- |
15 KVA |
ATT 15 KVA |
300X150X270 |
210 |
42 |
--- |
20 KVA |
ATT 20 KVA |
360X170X340 |
300 |
55 |
--- |
25 KVA |
ATT 25 KVA |
360X180X340 |
320 |
61 |
--- |
30 KVA |
ATT 30 KVA |
420X200X350 |
360 |
69 |
--- |
40 KVA |
ATT 40 KVA |
420X220X350 |
400 |
90 |
--- |
50 KVA |
ATT 50 KVA |
420X240X350 |
500 |
104 |
--- |
75 KVA |
ATT 75 KVA |
480X240X430 |
854 |
152 |
--- |
100 KVA |
ATT 100 KVA |
480X260X430 |
1200 |
170 |
--- |
|
|